I'm currently getting familiar with PLC's, the WAGO 750-8206 PLC in particular. It offers a linux OS and can run CoDeSys programs. There are some I/O modules attached to the controller: 750-530, 750-430 and 750-600. What I would like to know is this:
Is it possible to write a C++ linux application that runs on the PLC and gets/sets the digital inputs and outputs?
Even better: can I write a CoDeSys program that "talks to the I/O's" and handles all the logic and at the same time can be accessed by a C++ linux program? THe idea is this: I would like the CoDeSys program to check for let's say two digital inputs. If both are high, a variable should be set to a defined value. The linux application should be able to read that variable and conduct further processing (such as sending JSon data to a server or similar).
Also, I would need to be able to send commands from the linux application to the CoDeSys program in order to switch digital outputs (or set values on analog outputs etc) when the linux application receives a message that triggers the command.
Any thoughts and comments on this topic are greatly appreciated as I am completely new to this topic. Thanks in advance!
The actual situation has changed into the opposite of the previous answer.
WAGO's recent Board Support Packages and Documentation actively support you in making changes and extensions to the PLC200 line. Specifically the WAGO 750-8206 and 17 (as of March 2016) other PLCs :
wago.us -> Products -> Components for Automation -> Modular WAGO-I/O-SYSTEM, IP 20 (750/753 Series)
What you have to do is get in touch with them and ask for their latest Board Support Package (BSP) for the PLC200 line.
I quote from the previous answer and mark the changes, my additions are in bold.
Synopsis
- Could you hack a PFC200 and get custom binaries executed?
ProbablyAbsolutely yes. As long as the program is content to run on the Linux-3.6.11 kernel and glibc-2.16 and is compiled for the "armhf" API, any existing ARM application, provided you also copy the libraries it uses as well, will just run without even compiling it specifically for the PFC200.- Would it be easy or quick?
No. Yes, if you have no fear of the Linux Command line. It is as easy as using the Cross Compiler provided by the Board Support Package (BSP) with the provided C-libraries and then run this to transfer your program to the PFC's flash and run it:scp your-program root@PFC200:/usr/bin ssh root@FC200 /usr/bin/your-programOf course, you can use Eclipse CDT with the Cross Toolchain for the PFC200 and configure Eclipse to do do remote run and debug.- Will this change in the future?
Maybe. Remember that PFC200 is fairly new in North America.It has, PFC200 has appeared in September 2014
The public HOWTO Building FORTE for Wago describes how to use the initial BSP to run FORTE, which is the IEC 61499 run-time environment of 4DIAC (link: sf.net/projects/fordiac ), an open source PLC environment allowing to implement industrial control solutions in a vendor neutral way. 4DIAC implements IEC 61499 extending IEC 61131-3 with better support for controller to controller communication and dynamic reconfiguration.
In case you want to access the KBUS (which talks to the I/Os) directly, you have to know that currently only one application can be in charge of KBUS.
So either CODESYS, or FORTE, or your own KBUS application can be in charge of the KBUS.
The BSP from 2015 has many examples and demos how to use all the I/O of the PLC200 (KBUS, CAN, MODBUS, PROFIBUS as well as the Switches and LEDs on the PFC200 directly). Sources for the kernel and with all kernel drivers and the other Open Source components is provided and compiled in the Board Support Package (BSP).
But, the sources for the libraries and tools developed from scratch by WAGO and are not based on GPL/Open Source code are not provided: These include the Application Device Interface(ADI)/Device Abstraction Layer(DAL) libraries which do CANopen, PROFIBUS-Slave and KBus (which is used all PLC I/O modules connected to the main PLC unit)
While CANopen is using the standard Linux Socketcan API to talk to the kernel and you could just write a normal socketcan program using the provided libsocketcan, the KBus API is an WAGO-specific invention and there, you'd have to do some reverse-engineering if you'd not want to use WAGO's DAL for accessing all the electrical I/O of the PLC, but the DAL is documented and examples how to use it are provided in the BSP.
If you use CODESYS however, there is an "codesys_lib_demo-0.1" example library which shows how to provide a library for CODESYS to use.